DPN leakage protective breaker, protective breaker is used in the single phase residence circuit of AC 50Hz/60Hz, rated voltage 230V, used as electron shock protection. It can protect civil electron circuit form overload and short circuit. This product has advantages of small volume, high breaking capacity zero, and live wire connected opposite. This product conforms to IEC61009 and GB16917 standards.
Main technical parameter:
Rated current(A):6,10,16,20,25,32
No. of pole:1+N
Rated voltage (V):230
Rated current of frame:32
Rated leakage operating:30
Rated leakage non-operating current:15
Rate leakage breaking time:≤0.1s
Breaking capacity(A):3000
Overload Trip Charcteristic
Testing curret
(A) |
Limited
time |
Pre-engage
resu1t |
Start
situation |
Note |
| 1.13In |
t≥1h |
Non-trip |
cold state
|
The current rise steadily to a
fixed value within 5s |
| 1.45In |
t1h |
trip |
heat state |
| 2.25In |
Ist60s |
trip |
cold state |
Open the supplementary switch,
connect the power |
| 5In |
t≥0.1s |
non-trip |
cold state |
Open the supplementary switch,
connect the power |
| 10In |
t 0.1s |
trip |
cold state |
Open the supplementary switch,
connect the power |
Rated current
(A) |
Pole |
Rated voltage
(V) |
Rated current off
rame current
(A) |
Rated leakage
operating current
(mA) |
Rated leakage non-
operating current
(mA) |
Rated leakage
breaking time
(s) |
Breaking capacity
(A) |
6,10,16,
20,25,32 |
1P+N |
220 |
32 |
30 |
15 |
≤0.1s |
4500 |
|